Eurotherm 3116 PID Betriebsanweisung Seite 9

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 40
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 8
8
ENG
3116 User Guide Part No. HA028005ENG Issue 2.0 May 04
3.2 Wire Sizes
The screw terminals accept wire sizes from 0.5 to 1.5 mm (16 to 22AWG). Hinged covers prevent hands or metal making
accidental contact with live wires. The rear terminal screws should be tightened to 0.4Nm (3.5lb in).
3.3 PV Input (Measuring Input)
1. Do not run input wires together with power cables
2. When shielded cable is used, it should be grounded at one point only
Any external components (such as zener barriers, etc) connected between sensor and input terminals may cause errors in
measurement due to excessive and/or un-balanced line resistance or possible leakage currents
3.3.1 Thermocouple Input
For thermocouple input use the correct compensating cable preferably shielded
3.3.2 RTD Input
The resistance of the three wires must be the same. The line resistance may cause errors if it is greater than 22
3.3.3 Linear Input (mA or V)
A line resistance for voltage inputs may cause measurement errors
For volts input an external module is required. Input resistance 100K.
For mA input
connect burden resistor of 2.49 across the + and - input as shown
Seitenansicht 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 39 40

Kommentare zu diesen Handbüchern

Keine Kommentare