3116 User Guide Part No. HA028005ENG Issue 2.0 May 04
ENG
5
1.3 Step 1: Installation
This instrument is intended for permanent installation, for indoor use only, and enclosed in an electrical panel
Select a location which is subject to minimum vibrations and the ambient temperature is within 0 and 55
o
C (32 - 122
o
F)
The instrument can be mounted on a panel up to 15mm thick
To ensure IP65 and NEMA 4 front protection, mount on a non-textured surface.
Please read the safety information in section 4 before proceeding and refer to the EMC Booklet part number HA025464
for further installation information.
1.3.1 Panel Mounting the Controller
1. Prepare a square cut-out in the mounting panel to the size
shown. If a number of controllers are to be mounted in
the same panel they should be spaced as shown.
2. Fit the IP65 sealing gasket, if required, behind the front
bezel of the controller
3. Insert the controller through the cut-out
4. Spring the panel retaining clips into place. Secure the
controller in position by holding it level and pushing both
retaining clips forward.
5. Peel off the protective cover from the display
1.3.2 To Remove the Controller from its Sleeve
The controller can be unplugged from its sleeve by easing the
latching ears outwards and pulling it forward out of the sleeve.
When plugging it back into its sleeve, ensure that the latching ears click back into place to maintain the IP65 sealing.
45 mm - 0.0 + 0.6
1.77 in -0.00, +0.02
10mm (0.4 in)
38mm (1.5 in)
(Not to scale)
Recommended minimum
spacing of controllers